98 Series Automatic Strainers

98 Series Automatic Strainers

StrainerCarbon Steel, Stainless 304, Stainless 316

Key Features

  • Automatic, Motorized Self-Cleaning
  • True turn-key design
  • Lowest cost of ownership in the industry
Request Quote

Overview

Automatic, motorized self-cleaning strainers offering continuous removal of debris while maintaining full-time, uninterrupted flow. Offset inlet/outlet orientation, low pressure losses, and configurable controls allow the unit to adapt to changing process conditions.

How It Works

Unfiltered fluid enters the strainer through the inlet and flows into the centre of a wedge wire strainer basket.

Particulate collects on the screen as clean fluid passes through.

As differential pressure increases to the setpoint, the cleaning cycle initiates automatically.

An internal scraper (blades or brushes) rotates against the screen, removing buildup and directing it to the bottom sump.

A fast-acting blowdown valve opens to flush out collected solids; clean flow is uninterrupted during the cycle.

Clean fluid exits via the outlet toward the next process stage.

Applications

  • Cooling tower closed loop
  • Cooling water, once through (e.g. large Power Gen cooling water intake)
  • Pump-seal cooling water
  • Firewater pump protection
  • Lube oil systems
  • Industrial produced water
  • Renewable fuel feedstock (coarse screening at offloading), (fine screening downstream)
  • Steel mills & foundries, quench water filtration
  • Industrial wash stations (protecting spray nozzles)
  • Produced water & salt water disposal (SWD)
  • Specialty designs available for SWD service
  • Pulp & paper
  • Miscella filtration & separation (-50°F methanol service)
  • Chemical process screening contact us with your application

Control Level Options

L1: Standard Controller

Power Input: 120VAC, single phase
Control Panel: NEMA 4 enclosure, Siemens PLC & HMI
Purge Valve: Electric
Automation:
  • Field adjustable: DP setpoint, clean cycle duration, purge duration
  • Manual override

L2: Automatic, configurable

Power Input: Any voltage (120V/240V, 380V, 480V, 575V)
Control Panel: NEMA 4 or 4X, any PLC & HMI (Siemens, Allen-Bradley, Omron, ABB,etc.)
Purge Valve: Electric (pneumatic optional)
Automation:
  • Customizable automation package to match your process requirements

L3: Automatic, Hazardous Area

Power Input: Any voltage (120V/240V, 380V, 480V, 575V)
Control Panel: NEMA 7 or Pressure+Purge Panel, any PLC & HMI (Siemens, Allen-Bradley, Omron, ABB,etc.)
Purge Valve: Electric (pneumatic optional)
Automation:
  • Full scope automation package to match your process requirements